Industrial Process Controllers & Monitors
alpha-COND 1000 1/4 DIN Conductivity Controller
Ten Selectable Conductivity Measurement Ranges in one controller via its IP54 front panel. High-level accuracy of ±1% of full scale can be obtained with appropriate cells and correct temperature coefficient
User-Customization through Advanced Setup Menu offers flexibility in matching the controller's functions to suit individual's specific requirement
Choice of Cell Constant (0.01, 0.1, 1.0, 10.0) for accurate control in any solution
Hold Relay for use with float switches/flow switches and other controllers as a failsafe function
Two Level Password Protection prevents un authorized tampering with settings
0 to 2000 Second Time Delay Adjustment on control and alarm delays
Galvanically Isolated Scalebale 0-20/4-20 mA Outputs
Wash Contact Relay controls electrodes cleaning systems at desired duration and frequency
Adjustable Hysteresis (Dead Band) prevents rapid contact switching near set point
Non-Volatile Memory retains all stored parameters and calibration data even if power fails
Line Resistance Compensation against intrinsic cable resistance for longer cable connection
Large Dual Display shows measurement with temperature simultaneously - features clear multiple icons, set points, and status messages
Choice of Temperature Sensor Pt100/Pt1000 with 2-wire or 3-wire temperature input selection
Easy Installation and Wiring with detachable plug-in connectors
Applications:
General: Use for virtually any batch or online applications where rapid, accurate control. Great for OEM/system integrator.
Industrial: Use in applications involving agriculture, chemical processing, boiler and water heaters, wafer-fab, microprocessor manufacturing, pharmaceuticals, pulp and paper industries, and bleach manufacturing.
Water Purification/Treatment: Use to treat batches of incoming process water, ultrapure water, boiler and feed water control.
Regulatory: Hook up to recorder for regulatory compliance data collection.
Specifications:
|
Product
Specification
|
Description
|
|
Conductivity Range
|
0.000 to 1.999 µS/cm
0.01 µS/cm
0.1 µS/cm
1 µS/cm
5 µS/cm
0.01 mS/cm
0.1 mS/cm
|
0.001 µS/cm
0.01 µS/cm
0.1 µS/cm
1 µS/cm
5 µS/cm
0.01 mS/cm
0.1 mS/cm
|
|
Accuracy
|
±1 % full scale
|
|
Temperature Range
|
-9.9 to 125 °C
|
|
Resolution & Relative Accuracy
|
0.1 °C & ±0.5 °C
|
|
Temperature Sensor
|
Pt 100/ Pt 1000 (jumper selectable)
|
|
Temperature Compensation
|
Auto / Manual (reference at 25
°C)
|
|
Set Point
and Controller Functions
|
|
Function
|
Limit / Proportional (pulse or
frequency) controller
|
|
Switching Hysteresis
|
0 to 10% full scale
|
|
Pickup / Dropout Delay
|
0 to 2000 seconds
|
|
Contact Outputs, Controller
|
2 potential free change-over contacts
|
|
Switching Voltage / Current /
Power
|
Max 250 VAC / Max 3A / Max 600VA
|
|
Alarm
Functions
|
|
Function (Switchable)
|
Launching or Pulse
|
|
Pickup Delay
|
0 to 2000 seconds
|
|
Switching Voltage / Current /
Power
|
Max 250 VAC / Max 3A / Max 600VA
|
|
Electrical
Data and Connections
|
|
Power requirement
|
110/ 220 VAC (jumper selection)
|
|
Frequency
|
48 to 62Hz
|
|
Signal Output
|
0/4 to 20mA, galvanically isolated
|
|
Load
|
Max. 600 Ω
|
|
Connection Terminal
|
Terminal blocks 5-pole/ 17-pole,
removable
|
|
Main Fuse/ Fine Wire Fuse
|
Slow-blow 250 V/ 100 mA
|
|
EMC Specifications
|
|
Emitted Interference
|
According to EN 50081-1
|
|
Immunity to Interference
|
According to EN EN 50082-1
|
|
Environmental
Conditions
|
|
Maximum Relative Humidity
|
10 to 95%, non-condensing
|
|
Ambient Temp. Operating Range
|
0 to 50 °C
|
|
Mechanical
Specifications
|
|
Dimensions
|
175 x 96 x 96 mm
|
|
Weights
|
Max. 0.7kg
|
|
Material
|
ABS with polycarbonate
|
|
Insulation
|
IP 54/ IP 40
|
|