Product
Specification
|
Description
|
|
pH Range
|
-2.00 to 16.00 pH
|
|
Resolution & Accuracy
|
0.01 pH & ±0.01 pH
|
|
mV Range
|
-1000 to 1000 mV / 0 to 100% (for
-100 to 100 mV)
|
|
Resolution & Accuracy
|
1 mV / 0.1% & ±1 mV / ±0.2%
|
|
Temperature Range
|
-10.0 to 110 °C (14.0 to 230.0 °F)
|
|
Resolution & Relative Accuracy
|
0.1 °C / °F &
±0.5 °C / ±1.0 °F
|
|
Temperature Sensor
|
NTC 300; 2 wire
|
|
Temperature Compensation
|
Auto / Manual
(Independent Process / CAL Temperature)
|
|
Set
Point and Controller Functions
|
|
Set Point 1 (SP1) / Set Point 2 (SP2)
|
-2.00 to 16.00 pH or 0 to 100% or
-1000 to 1000 mV
|
|
Hysteresis
|
0.1 to 1 pH or 1 to 10.0% / 10 to
100 mV
|
|
Function (Switchable)
|
P/PI control (Pulse Length / Pulse
Frequency);
Limit Control; Off
|
|
Proportional Range
|
10 to 500%
|
|
Integral Action Time (IAT)
|
0 to 999.9 minutes
|
|
Adjustable Period with Pulse Length
Controller
|
0.5 to 20 seconds
|
|
Adjustable Period with Pulse Frequency
Controller
|
60 to 120 pulses/min
|
|
Pickup / Dropout Delay
|
0 to 2000 seconds
|
|
Wash Cycle
|
0.1 to 200.0 hours
|
|
Wash Duration
|
1 to 2000 seconds
|
|
Contact Outputs, Controller
|
1 SPDT, 3 SPST relays
|
|
Switching Voltage / Current / Power
|
Max 250 VAC / Max 3A / Max 600VA
|
|
Alarm
Functions
|
|
Function (Switchable)
|
Steady or Fleet (Pulse)
|
|
Pickup Delay
|
0 to 2000 seconds
|
|
Display
|
|
LCD
|
UV coat, backlit 14 segments display
with symbols for status information
|
|
Backlight
|
On/Off selectable with four levels
of brightness control
|
|
Electromagnetic
Compliance (EMC) Specifications
|
|
Emitted Interference
|
According to EN 61326
|
|
Immunity to Interference
|
According to EN 61326
|
|
Environmental
Conditions
|
|
Ambient Temperature Operating Range
|
0 to 40 °C
|
|
Maximum Relative Humidity
|
80% up to 31 °C decreasing linearly
to 50%
at 40 °C
|
|
Power Supply
|
|
Input
|
80 to 250 VAC/DC 50/60 Hz Approx.
10 VA
|
|
Main Fuse
|
315 mA time delay, 250 V,
Bussmann BK/GDC-315 mA
|
|
Pollution Degree
|
2
|
|
Transient Overvoltage Category
|
II
|
|
Electrical
Data and Connections
|
|
Transmitter Function
|
Two 0/4 to 20 mA scalable outputs
for pH/ORP and temperature, galvanically isolated
|
|
CU 22 Function
|
22 mA current output
|
|
Isolated Output Voltage
|
+12V ±0.5 V (Max 50 mA)
|
|
Hold Function Switch
|
To freeze output current and deactivate
control relays
|
|
Load
|
Max 600 W
|
|
Differential pH/ORP Input
|
2 pin terminal
|
|
Connection Terminal
|
5-pin, 8-pin, 9-pin and 13-pin terminal,
detachable blocks
|
|
Mechanical
Specifications
|
|
Dimensions (W x H x D)
|
144 x 144 x 110 mm
|
|
Weight
|
950g (unit) / 1100g (Packed)
|
|
Environmental Rating
|
IP65 (NEMA 4X)
|